Technical specifications Elco system cable
| Configuration | 14 x 2 x 0.75 mm² acc. to Shell DEP. 32.37.20.31- GEN December 1997 |
| Core identification code | Colored acc. to Shell DEP. 32.37.20.31-GEN December 1997 |
| Stranding | 24 x 0.2 mm tin plated copper |
| Number of conductors | 28, twisted in 14 pairs |
| Insulation | PVC insulation Ø 2.3 mm |
| Diameter jacket | 2.3 mm |
| Screening | 2 x aluminum Mylar foil 23/25 µm with drain wire 16 x 0.2 mm tin plated copper |
| Jacket | PVC compound, flame retardant |
| Weight | 390 kg/km |
| Temperature range | -30 ºC tot +90 ºC |
| Length | To be specified |
| Diameter | 18.4 mm |
| Color | Grey |
| Loop resistance | 23 Ohm/km at 20 ºC |
| Capacity | ± 80 nF/km |
| Insulation resistance | >1000 Mohm × km |
| Test voltage | 1500 VDC |
| Operating voltage | 250 V |
| RoHS | The cable is RoHS compliant according EU directive 2002/95/EG |
Technical specifications Elco connector
| Type | Part number |
| Empty connector body female 30 P | 00-8027-030-000-003 |
| Cover 90 degrees | 30-8027-8935-02-113 |
| Crimp-on gold contacts | 60-8017-0323 |
| Locking code | 1-1* |
*Other combinations on request
Ordering details
| Type E30/28 with 1 connector of 90 degrees | Order number 83028-90-1 |
| Type E30/28 with 2 connector of 90 degrees | Order number 83028-90-2 |